MiCOM P632
Frequency Protection
Operate values f<>

± 30 mHz (f nom = 50 Hz)

± 40 mHz (f nom = 60 Hz)

Operate values df/dt

± 0.1 Hz/s (f nom = 50 or 60 Hz)