MiCOM P632
Configuring the LED Indicators

One binary signal can be assigned to each of the red and green LED color indications. The same binary signal can be assigned to several LED indicators (or colors), if required.

LED indicator

Label

Configuration

H 1 (green)

HEALTHY

Not configurable. H 1 indicates the operational readiness of the P632 (supply voltage is present).

H 17 (red)

EDIT MODE

Not configurable. H 17 indicates the input (edit) mode. Only when the P632 is in this mode, can parameter settings be changed by pressing the “Up” and “Down” keys. (See Chapter “Display and Keypad”)

H 2 (amber)

OUT OF SERVICE

Permanently configured with function MAIN: Blocked/faulty.

H 3 (amber)

ALARM

Permanently configured with function SFMON: Warning (LED).

H 4 (red)

TRIP

With the P632 this LED indicator is customarily configured with function MAIN: Gen. trip signal, but the configuration may be modified.

H 4 (green)

Function assignment to this green LED indicator is freely configurable.

H 5 to H 16

For each of these LED indicators both colors (red & green) may be configured freely and independently.