MiCOM P632
Overload Logging

Protection signals during an overload event are logged in chronological order with reference to the specific event. A total of eight overload events, each involving a maximum of 200 start or end signals, can be stored in the non-volatile overload memories. After eight overload events have been logged, the oldest overload log will be overwritten, unless memories have been cleared in the interim. If more than 199 start or end signals have occurred during a single overload event, then OL_RC: Overl. mem. overflow will be entered as the last signal.

In addition to the signals, the measured overload data will also be entered in the overload memory.

The overload logs can be read from the local control panel or through the PC or communication interfaces.