Phase Current Stages

The three phase currents are monitored by the P632 with three-stage functions to detect when they exceed the set thresholds. One of two different threshold types can be active. The “dynamic” thresholds are active for the set hold time for the “dynamic parameters” (see Chapter “Activation of “Dynamic Parameters””) and the “normal” thresholds are active when no hold time is running. If the current exceeds the set thresholds in one phase, timer stages are started. Once the time delays have elapsed, a trip signal is issued. The timer stages can be blocked by appropriately configured binary signal inputs.

The first stage of the DTOC protection function can optionally be blocked by the inrush stabilization function of differential protection.

graphics/xhelptemp/svg2png/svg_0339_104_resolved.png

Fig. 3-113: Phase current stages