MiCOM P632
Readiness of Thermal Overload Protection

Thermal overload protection will issue the THRM1: Not ready signal if one of the following conditions applies:

Thermal overload protection is disabled.

Thermal overload protection is blocked because of a fault in the coolant temperature (ambient) acquisition.

Thermal overload protection is blocked because of an incorrect setting.

The thermal replica is blocked via an appropriately configured binary signal input.

graphics/xhelptemp/svg2png/svg_0354_119_resolved.png

Fig. 3-132: THRM1: Not ready