MiCOM P632
Assigning the Trip
Command
|
Which of the trip commands is to be used as a start criterion for the respective CBF function may be selected by setting parameters:
Address |
Description |
Range of Values |
---|---|---|
022 202 |
CBF_1: Fct.assign. starting |
MAIN: Gen. trip signal 1 MAIN: Gen. trip signal 2 MAIN: Gen. trip signal 3 MAIN: Gen. trip signal 4 |
022 216 |
CBF_2: Fct.assign. starting |
The functional range made available by the circuit breaker failure protection function CBF_1 is documented in the following description. Function group CBF_2 provides the same functional range.