MiCOM P632
Current-Measuring Inputs

When connecting the system transformers, it must be ensured that the secondary nominal currents of the system and the device correspond.

graphics/symbols/Warning.png WARNING

The secondary circuit of live system current transformers must not be opened! If the secondary circuit of a live CT is opened, there is the danger that the resulting voltages will endanger personnel and damage the insulation.

graphics/symbols/Warning.png WARNING

For pin-terminal connection devices, the terminal block for system current transformer connection is not a shorting block! Therefore always short-circuit the system current transformers before loosening the threaded terminals.