MiCOM P632
Changing Parameters

If all the conditions for a value change are satisfied, the desired setting can be entered.

 

Control Step / Description

Control Action

Display

Step 0

Example of a display.

In this example, the change-enabling function is activated and the protective function is disabled, if necessary.

 
Oper/CtrlTest/LOC
Param. change enabl.
Yes

Step 1

Select the desired setting by pressing the keys.

graphics/xhelptemp/svg2png/svg_0263.png
Par/Conf/LOC
Autom. return time
    50000 s

Step 2

Press the ENTER key. The LED indicator labeled EDIT MODE will light up. The last digit of the value is highlighted by a cursor (underlined).

graphics/xhelptemp/svg2png/svg_0255.png
graphics/xhelptemp/svg2png/svg_0261.png
Par/Conf/LOC
Autom. return time
    50000̲ s

Step 3

Press the “left” or “right” keys to move the cursor to the left or right.

graphics/xhelptemp/svg2png/svg_0264.png
Par/Conf/LOC
Autom. return time
    5000̲0 s

Step 4

Change the value highlighted by the cursor by pressing the “up” and “down” keys. In the meantime the device will continue to operate with the old value.

graphics/xhelptemp/svg2png/svg_0262.png
Par/Conf/LOC
Autom. return time
    5001̲0 s

Step 5

Press the ENTER key. The LED indicator labeled EDIT MODE will go out and the device will now operate with the new value. Press the keys to select another setting for a value change.

graphics/xhelptemp/svg2png/svg_0255.png
Par/Conf/LOC
Autom. return time
    50010 s

Step 6

If you wish to reject the new setting while you are still entering it (LED indicator labeled EDIT MODE is on), press the CLEAR key. The LED indicator will go out and the device will continue to operate with the old value. A further setting can be selected for a value change by pressing the keys.

graphics/xhelptemp/svg2png/svg_0256.png
Par/Conf/LOC
Autom. return time
    50000 s