MiCOM P632
Password-Protected Control Actions
|
Certain actions from the local control panel such as a manual trip command for testing purposes can only be carried out by entering a password so as to prevent unwanted output even though the global change-enabling function has been activated (see section “Change-Enabling Function”).
This setup is designed to prevent accidental output and applies even when the global change-enabling function has been activated. The password consists of a pre-defined sequential key combination entered within a specific time interval. If the password has been changed by the user (see section “Changing the Password”), the following description will apply accordingly.
|
Control Step / Description |
Control Action |
Display |
---|---|---|---|
Step 0 |
In the menu tree “Oper/CtrlTest/MAIN”, select the parameter MAIN: Man. trip cmd. USER. |
|
Oper/CtrlTest/MAIN |
Step 1 |
Press the ENTER key. Eight asterisks (*) appear in the fourth line of the display. |
Oper/CtrlTest/MAIN | |
Step 2 |
Press the following keys in sequence: “Left” |
Oper/CtrlTest/MAIN | |
|
“Right” |
Oper/CtrlTest/MAIN | |
|
“Up” |
Oper/CtrlTest/MAIN | |
|
“Down” The display will change as shown in the column on the right. |
Oper/CtrlTest/MAIN | |
|
Now press the enter key. The LED indicator labeled EDIT MODE will light up. This indicates that the setting can now be changed by pressing the “up” or “down” keys. |
Oper/CtrlTest/MAIN | |
Step 3 |
Change the setting to execute. |
Oper/CtrlTest/MAIN | |
Step 4 |
Press the enter key again. The LED indicator labeled EDIT MODE will go out. The unit will execute the command. |
Oper/CtrlTest/MAIN | |
Step 5 |
As long as the LED indicator labeled EDIT MODE is on, the control action can be terminated by pressing the CLEAR key. The LED indicator labeled EDIT MODE will be extinguished. |