MiCOM P632
Dataset Definitions
|
|
Parameter |
|
| |
---|---|---|---|---|
Dataset Definitions |
Name |
|
| |
|
Explicitly (and uniquely) assigned name for the dataset. |
| ||
|
Location |
|
| |
|
Saving datasets at System/LLN0 is compulsory. |
| ||
|
Contents |
|
| |
|
Content (data objects, data attributes) of a dataset. The “GOOSE Capacity” display allows for checking the length of a dataset for less than 1500 bytes to permit transmission in GOOSE messages. The display is irrelevant when the dataset is only used in reports. Note: It is not possible to read the IEC configuration back from the P139 if the “Dataset” sizes exceed the GOOSE size limit significantly. Therefore it is recommended to limit the “Dataset” size(s) to max. 120% of the GOOSE capacity. |
| ||
|