MiCOM P632
IED Details
|
The category “IED Details” contains several settings that characterize the device as well as the SCL file, which identifies the IEC 61850 configuration.
|
Parameter |
Default Value |
|
|
---|---|---|---|---|
SCL Details |
SCL File ID |
PX 632 |
|
|
|
Identification of the .MCL configuration file. If required, this preset value may be modified by, for example, entering a bay name. |
| ||
|
SCL File Version |
240 |
|
|
|
Specific value to identify the IEC 61850 data model and configuration. If required, this preset value may be modified by, for example, identifying the revision states during engineering. |
| ||
|
|
Parameter |
Default Value |
Address |
|
---|---|---|---|---|
IED Details |
Name |
TEMPLATE |
104 057 |
|
|
Explicitly assigned device name for the function in the system (IED); is part of the Logical Device Name. Important note: According to the IEC standard the name must consist of only letters (A..Z, a..z), digits (0..9) and underscore characters (_), and the name must start with a letter. Note that a non-standard name causes problems with the IEC 61850 communication. |
| ||
|
|
Parameter |
|
| |
---|---|---|---|---|
Template Details |
ICD Template |
|
| |
|
SCL Schema Version |
|
| |
|
Description |
|
| |
|
Type |
|
| |
|
Configuration Revision |
|
| |
|
Supported Models |
|
| |
|
The values listed in the column “Template Details” only provide information. They are preset and cannot be modified. |
| ||
|