MiCOM P632
Selection of Standard Information Numbers in Monitor Direction
System Functions in Monitor Direction
 

INF

Description

[✓]

<0>

End of general interrogation

[✓]

<0>

Time synchronization

[✓]

<2>

Reset FCB

[✓]

<3>

Reset CU

[✓]

<4>

Start / restart

[ ]

<5>

Power on

Status Indications in Monitor Direction
 

INF

Description

P632 Designations

(Address) Description

[ ]

<16>

Auto-recloser active

 

[ ]

<17>

Teleprotection active

 

[✓]

<18>

Protection active

(003 030) MAIN: Device on-line

[✓]

<19>

LED reset

(021 010) MAIN: Reset indicat. USER

[✓]

<20>

Blocking of monitor direction

(037 075) COMM1: Sig./meas.val.block.

[✓]

<21>

Test mode

(037 071) MAIN: Test mode

[ ]

<22>

Local parameter setting

 

[✓]

<23>

Characteristic 1

(036 090) PSS: PS 1 active

[✓]

<24>

Characteristic 2

(036 091) PSS: PS 2 active

[✓]

<25>

Characteristic 3

(036 092) PSS: PS 3 active

[✓]

<26>

Characteristic 4

(036 093) PSS: PS 4 active

[✓]

<27>

Auxiliary input 1

(034 000) LOGIC: Input 1 EXT

[✓]

<28>

Auxiliary input 2

(034 001) LOGIC: Input 2 EXT

[✓]

<29>

Auxiliary input 3

(034 002) LOGIC: Input 3 EXT

[✓]

<30>

Auxiliary input 4

(034 003) LOGIC: Input 4 EXT

Monitoring Signals (Supervision Indications) in Monitor Direction
 

INF

Description

P632 Designations

(Address) Description

[ ]

<32>

Measurand supervision I

 

[ ]

<33>

Measurand supervision V

 

[ ]

<35>

Phase sequence supervision

 

[✓]

<36>

Trip circuit supervision

(The message content is formed from the OR operation of the individual signals.)

(041 200) SFMON: Relay Kxx faulty

[ ]

<37>

I>> back-up operation

 

[✓]

<38>

VT fuse failure

(004 061) MAIN: M.c.b. trip V EXT

[ ]

<39>

Teleprotection disturbed

 

[✓]

<46>

Group warning

(036 100) SFMON: Warning (relay)

[✓]

<47>

Group alarm

(004 065) MAIN: Blocked/faulty

Earth Fault Indications in Monitor Direction
 

INF

Description

P632 Designations

(Address) Description

[ ]

<48>

Earth fault A

 

[ ]

<49>

Earth fault B

 

[ ]

<50>

Earth fault C

 

[ ]

<51>

Earth fault forward, i.e. line

 

[ ]

<52>

Earth fault reverse, i.e. busbar

 
Fault Indications in Monitor Direction
 

INF

Description

P632 Designations

(Address) Description

[ ]

<64>

Start / pick-up A

 

[ ]

<65>

Start / pick-up B

 

[ ]

<66>

Start / pick-up C

 

[ ]

<67>

Start / pick-up N

 

[✓]

<68>

General trip

(036 071) MAIN: Gen. trip command 1

[ ]

<69>

Trip A

 

[ ]

<70>

Trip B

 

[ ]

<71>

Trip C

 

[ ]

<72>

Trip I>> (back-up operation)

 

[ ]

<73>

Fault location X in ohms

 

[ ]

<74>

Fault forward/line

 

[ ]

<75>

Fault reverse/busbar

 

[ ]

<76>

Teleprotection signal transmitted

 

[ ]

<77>

Teleprotection signal received

 

[ ]

<78>

Zone 1

 

[ ]

<79>

Zone 2

 

[ ]

<80>

Zone 3

 

[ ]

<81>

Zone 4

 

[ ]

<82>

Zone 5

 

[ ]

<83>

Zone 6

 

[✓]

<84>

General starting

(036 000) MAIN: General starting

[ ]

<85>

Breaker failure

 

[✓]

<86>

Trip measuring system A

(041 002) DIFF: Trip signal 1

[✓]

<87>

Trip measuring system B

(041 003) DIFF: Trip signal 2

[✓]

<88>

Trip measuring system C

(041 004) DIFF: Trip signal 3

[ ]

<89>

Trip measuring system N

 

[ ]

<90>

Trip I>

 

[ ]

<91>

Trip I>>

 

[ ]

<92>

Trip IN>

 

[ ]

<93>

Trip IN>>

 
Auto-Reclosure Indications in Monitor Direction
 

INF

Description

P632 Designations

(Address) Description

[ ]

<128>

CB ‘on’ by AR

 

[ ]

<129>

CB ‘on’ by long-time AR

 

[ ]

<130>

AR blocked

 
Measurands in Monitor Direction
 

INF

Description

P632 Designations

(Address) Description

[ ]

<144>

Measurand I

 

[ ]

<145>

Measurands I, V

 

[ ]

<146>

Measurands I, V, P, Q

 

[ ]

<147>

Measurands IN, VEN

 

[ ]

<148>

Measurands IA,B,C, VA,B,C, P, Q, f

 
Generic Functions in Monitor Direction
 

INF

Description

[ ]

<240>

Read headings of all defined groups

[ ]

<241>

Read values or attributes of all entries of one group

[ ]

<243>

Read directory of a single entry

[ ]

<244>

Read value or attribute of a single entry

[ ]

<245>

General interrogation of generic data

[ ]

<249>

Write entry with confirmation

[ ]

<250>

Write entry with execution

[ ]

<251>