MiCOM P632
Bay type No. 8 Feeder bay with switch disconnector, single busbar
|
A11.200.R02
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(X0=X) & /(FctBl1=I) & /(FktSp2=I) |
X0 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) |
Tab. A-44: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(X0=X) & /(FctBl1=I) & /(FktSp2=I) |
X0 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) |
Tab. A-45: Bay Interlock Equations for Operation with Station Interlocking