MiCOM P632
Bay type No. 13 Feeder bay with switch disconnector / fuse unit, single busbar

A11.400.R02

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0141.png

Close(d)

U A02

K A02

X0 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

F (SIG_1: Signal S011)

U B05

/

Tab. A-58: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(X0=X) & /(FctBl1=I) & /(FktSp2=I)

X0

Open

(Q0=0)

Close(d)

(Q0=0)

Tab. A-59: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(X0=X) & /(FctBl1=I) & /(FktSp2=I)

X0

Open

(Q0=0)

Close(d)

(Q0=0)

Tab. A-60: Bay Interlock Equations for Operation with Station Interlocking