MiCOM P632
Bay type No. 21 Feeder bay with circuit breaker, single busbar
|
A13.105.R03
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I) |
Q1 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
Q8 |
Close(d) |
(Q0=0) & (Q1=0) |
Tab. A-89: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I) |
Q1 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
Q8 |
Close(d) |
(Q0=0) & (Q1=0) |
Tab. A-90: Bay Interlock Equations for Operation with Station Interlocking