MiCOM P632
Bay type No. 30 Feeder bay with switch disconnector, single busbar, direct motor control

A13.205.M03

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0152.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Q8 (DEV03)

Open

U A05

K A05

Close(d)

U A06

K A06

Mot.relay (SIG_1: Signal S012)

U B06

/

Shunt wd. (CMD_1: Command C011)

/

K B05

Mot.relay (CMD_1: Command C012)

/

K B06

Tab. A-121: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0)

Close(d)

(Q0=0) & (Q8=0)

Q8

Close(d)

(Q0=0) & (Q1=0)

Tab. A-122: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0)

Close(d)

(Q0=0) & (Q8=0)

Q8

Close(d)

(Q0=0) & (Q1=0)

Tab. A-123: Bay Interlock Equations for Operation with Station Interlocking