MiCOM P632
Bay type No. 33 Feeder bay with switch disconnector, single busbar

A13.205.R03

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0152.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Q8 (DEV03)

Open

U A05

K A05

Close(d)

U A06

K A06

Tab. A-130: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0)

Close(d)

(Q0=0) & (Q8=0)

Q8

Close(d)

(Q0=0) & (Q1=0)

Tab. A-131: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0)

Close(d)

(Q0=0) & (Q8=0)

Q8

Close(d)

(Q0=0) & (Q1=0)

Tab. A-132: Bay Interlock Equations for Operation with Station Interlocking