MiCOM P632
Bay type No. 66 Feeder bay with switch disconnector / fuse unit, double busbar

A21.404.R04

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0164.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Q2 (DEV03)

Open

U A05

K A05

Close(d)

U A06

K A06

X0 (DEV04)

Open

U B01

K B01

Close(d)

U B02

K B02

F (SIG_1: Signal S011)

U B05

/

Tab. A-244: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0) & (Q2=0)

Close(d)

(Q0=0) & (Q2=0)

Q2

Open

(Q0=0) & (Q1=0)

Close(d)

(Q0=0) & (Q1=0)

X0

Open

(Q0=0) & (Q1=0) & (Q2=0)

Close(d)

(Q0=0) & (Q1=0) & (Q2=0)

Tab. A-245: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FktSp2=I)

X0

Open

(Q0=0) & (Q1=0) & (Q2=0)

Close(d)

(Q0=0) & (Q1=0) & (Q2=0)

Tab. A-246: Bay Interlock Equations for Operation with Station Interlocking