MiCOM P632
Bay type No. 68 Feeder bay with switch disconnector / fuse unit, double busbar

A21.405.R01

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0165.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

/

Close(d)

U A04

/

Q2 (DEV03)

Open

U A05

/

Close(d)

U A06

/

X0 (DEV04)

Open

U B01

/

Close(d)

U B02

/

Q8 (DEV05)

Open

U B03

/

Close(d)

U B04

/

F (SIG_1: Signal S011)

U B05

/

Tab. A-250: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-251: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-252: Bay Interlock Equations for Operation with Station Interlocking