MiCOM P632
Bay type No. 95 Feeder bay with circuit breaker, double busbar
|
A23.106.R04
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FktSp2=I) |
Q1 |
Open |
(Q0=0) & (Q2=0) |
Close(d) |
(Q0=0) & (Q2=0) | |
Q2 |
Open |
(Q0=0) & (Q1=0) |
Close(d) |
(Q0=0) & (Q1=0) | |
Q9 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) |
Tab. A-332: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FktSp2=I) |
Q9 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) |
Tab. A-333: Bay Interlock Equations for Operation with Station Interlocking