MiCOM P632
Bay type No. 101 Feeder bay with switch disconnector, double busbar

A23.204.R01

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0174.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

/

Close(d)

U A04

/

Q2 (DEV03)

Open

U A05

/

Close(d)

U A06

/

Tab. A-349: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-350: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-351: Bay Interlock Equations for Operation with Station Interlocking