MiCOM P632
Bay type No. 113 Feeder bay with switch disconnector, double busbar

A23.207.R05

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0177.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Q2 (DEV03)

Open

U A05

K A05

Close(d)

U A06

K A06

Q9 (DEV04)

Open

U B01

K B01

Close(d)

U B02

K B02

Q8 (DEV05)

Open

U B03

K B03

Close(d)

U B04

K B04

Tab. A-385: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0) & (Q2=0)

Close(d)

(Q0=0) & (Q2=0)

Q2

Open

(Q0=0) & (Q1=0)

Close(d)

(Q0=0) & (Q1=0)

Q8

Close(d)

(Q9=0)

Q9

Open

(Q0=0)

Close(d)

(Q0=0) & (Q8=0)

Tab. A-386: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FktSp2=I)

Q8

Close(d)

(Q9=0)

Q9

Open

(Q0=0)

Close(d)

(Q0=0) & (Q8=0)

Tab. A-387: Bay Interlock Equations for Operation with Station Interlocking