MiCOM P632
Bay type No. 223 Feeder bay with circuit breaker, double busbar, direct motor control

A25.105.M03.2

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0181.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Q2 (DEV03)

Open

U A05

K A05

Close(d)

U A06

K A06

Q8 (DEV04)

Open

U B01

/

Close(d)

U B02

/

Mot.relay (SIG_1: Signal S012)

U B06

/

Shunt wd. (CMD_1: Command C011)

/

K B05

Mot.relay (CMD_1: Command C012)

/

K B06

Tab. A-412: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Open

(Q8=0)

Close(d)

/(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Q1

Open

(Q0=0) & (Q2=0)

Close(d)

(Q0=0) & (Q2=0) & (Q8=0)

Q2

Open

(Q0=0) & (Q1=0)

Close(d)

(Q0=0) & (Q1=0) & (Q8=0)

Tab. A-413: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Open

(Q8=0)

Close(d)

/(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Q1

Close(d)

(Q8=0)

Q2

Close(d)

(Q8=0)

Tab. A-414: Bay Interlock Equations for Operation with Station Interlocking