MiCOM P632
Bay type No. 123 Feeder bay with circuit breaker, double busbar

A25.105.R01.1

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0180.png

Close(d)

U A02

K A02

Q1 (DEV02)

Open

U A03

/

Close(d)

U A04

/

Q2 (DEV03)

Open

U A05

/

Close(d)

U A06

/

Q8 (DEV04)

Open

U B01

/

Close(d)

U B02

/

Tab. A-421: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Open

(Q8=0)

Close(d)

/(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-422: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Open

(Q8=0)

Close(d)

/(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-423: Bay Interlock Equations for Operation with Station Interlocking