MiCOM P632
Bay type No. 134 Bus sectionalizer bay with circuit breaker, single busbar

L11.100.R02

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0183.png

Close(d)

U A02

K A02

X01 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Tab. A-451: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(X01=X) & /(FctBl1=I) & /(FktSp2=I)

X01

Open

(Q0=0)

Close(d)

(Q0=0)

Tab. A-452: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Close(d)

/(X01=X) & /(FctBl1=I) & /(FktSp2=I)

X01

Open

(Q0=0)

Close(d)

(Q0=0)