MiCOM P632
Bay type No. 135 Bus sectionalizer bay with circuit breaker, single busbar
|
L11.104.R01
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(X01=X) & /(FctBl1=I) & /(FktSp2=I) |
Tab. A-461: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(X01=X) & /(FctBl1=I) & /(FktSp2=I) |
Tab. A-462: Bay Interlock Equations for Operation with Station Interlocking