MiCOM P632
Bay type No. 141 Bus sectionalizer bay with circuit breaker, single busbar
|
L11.120.R03
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FktSp2=I) |
X01 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
X02 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) |
Tab. A-494: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FktSp2=I) |
X01 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
X02 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) |
Tab. A-495: Bay Interlock Equations for Operation with Station Interlocking