MiCOM P632
Bay type No. 161 Bus sectionalizer bay with circuit breaker, double busbar
|
L21.101.R04.2
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FktSp2=I) |
Q21 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) | |
Q22 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) | |
X0 |
Open |
(Q0=0) & (Q21=0) & (Q22=0) |
Close(d) |
(Q0=0) & (Q21=0) & (Q22=0) |
Tab. A-569: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Close(d) |
/(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FktSp2=I) |
Q21 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) | |
Q22 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) | |
X0 |
Open |
(Q0=0) & (Q21=0) & (Q22=0) |
Close(d) |
(Q0=0) & (Q21=0) & (Q22=0) |
Tab. A-570: Bay Interlock Equations for Operation with Station Interlocking