MiCOM P632
Bay type No. 211 Bus coupler bay with circuit breaker, double busbar
|
Q25.105.R04
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Open |
(Q8=0) |
Close(d) |
/(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I) | |
Q10 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
Q20 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
Q8 |
Open |
(Q0=I) & (Q20=I) |
Close(d) |
(Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FktSp2=I) & (Q8=I) |
Tab. A-695: Bay Interlock Equations for Operation without Station Interlocking
Switchgear unit |
Control O/C |
Interlock equation |
---|---|---|
Q0 |
Open |
(Q8=0) |
Close(d) |
/(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FktSp2=I) | |
Q10 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
Q20 |
Open |
(Q0=0) |
Close(d) |
(Q0=0) & (Q8=0) | |
Q8 |
Open |
(Q0=I) & (Q20=I) |
Close(d) |
(Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FktSp2=I) |
Tab. A-696: Bay Interlock Equations for Operation with Station Interlocking