MiCOM P632
Bay type No. 217 Bus coupler bay with circuit breaker, double busbar

Q25.113.R05

Switchgear unit

Binary input

Output relay

 

Q0 (DEV01)

Open

U A01

K A01

graphics/0223.png

Close(d)

U A02

K A02

Q10 (DEV02)

Open

U A03

K A03

Close(d)

U A04

K A04

Q20 (DEV03)

Open

U A05

K A05

Close(d)

U A06

K A06

Q15 (DEV04)

Open

U B01

K B01

Close(d)

U B02

K B02

Q25 (DEV05)

Open

U B03

K B03

Close(d)

U B04

K B04

Tab. A-724: Assignment of Binary Inputs and Output Relays

Switchgear unit

Control O/C

Interlock equation

Q0

Open

(Q15=0) & (Q25=0)

Close(d)

/(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FktSp2=I)

Q10

Open

(Q0=0)

Close(d)

(Q0=0) & (Q15=0)

Q15

Open

(Q0=I) & (Q20=I)

Close(d)

(Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FktSp2=I) & (Q15=I)

Q20

Open

(Q0=0)

Close(d)

(Q0=0) & (Q25=0)

Q25

Open

(Q0=I) & (Q10=I)

Close(d)

(Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FktSp2=I) & (Q25=I)

Tab. A-725: Bay Interlock Equations for Operation without Station Interlocking

Switchgear unit

Control O/C

Interlock equation

Q0

Open

(Q15=0) & (Q25=0)

Close(d)

/(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FktSp2=I)

Q10

Open

(Q0=0)

Close(d)

(Q0=0) & (Q15=0)

Q15

Open

(Q0=I) & (Q20=I)

Close(d)

(Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FktSp2=I)

Q20

Open

(Q0=0)

Close(d)

(Q0=0) & (Q25=0)

Q25

Open

(Q0=I) & (Q10=I)

Close(d)

(Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FktSp2=I)

Tab. A-726: Bay Interlock Equations for Operation with Station Interlocking