Organization of the Recording Memories
|
▪ |
All signals relating to normal operation; from a total of 1024 different logic state signals. |
▪ |
The 1000 most recent signals. |
▪ |
All signals relevant for self-monitoring from a total of 1024 different logic state signals. |
▪ |
Up to 30 signals. |
▪ |
The 8 most recent overload events |
▪ |
All signals relevant for an overload event from a total of 1024 different logic state signals. |
▪ |
200 entries per overload event. |
▪ |
The 8 most recent ground fault events |
▪ |
All signals relevant for a ground fault event from a total of 1024 different logic state signals. |
▪ |
200 entries per ground fault event. |
▪ |
The 8 most recent faults. |
▪ |
All fault-relevant signals from a total of 1024 different logic state signals. |
▪ |
Sampled values for all measured currents and voltages |
▪ |
200 entries per fault event |
▪ |
max. number of cycles per fault can be set by user; 820 periods in total for all faults, that is 16.4 s (for fnom = 50 Hz) or 13.7 s (for fnom = 60 Hz). |
▪ |
As per Chapter “Resolution of the Fault Data Acquisition”, with maximum current dynamic ranges (100 Inom / 16 IN,nom) |