MiCOM P632
Environmental tests
|
Per IEC 60068-2-1
▪ |
-25°C (-13°F) storage (96 hours) |
▪ |
-40°C (-40°F) operation (96 hours) |
Per IEC 60068-2-2
▪ |
+85°C (185°F) storage (96 hours) |
▪ |
+85°C (185°F) operation (96 hours) |
Per IEC 60068-2-14
▪ |
Change of temperature, 5 cycles, 1°C / min rate of change |
Per IEC 60068-2-3
▪ |
56 days at ≤ 93% relative humidity and 40°C (104°F) |
Per IEC 60068-2-30
▪ |
Damp heat, cyclic (12 + 12 hours) 93 % relative humidity, +25°C … +55°C (77°F … 131°F) |
Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3
Industrial corrosive environment/ poor environmental control, mixed gas flow test.
▪ |
21 days at 75% relative humidity and 30°C (86°F) with exposure to elevated concentrations of H2S, NO2, Cl2 and SO2. |