MiCOM P632
Resistance Thermometer
|
Only PT 100 permitted for analog (I/O) module, mapping curve per IEC 75.1.
PT 100, Ni 100 or Ni 120 permitted for temperature p/c board (the RTD module).
▪ |
Value range: ‑40.0°C to +215.0°C (‑40°F to +419°F). |
▪ |
3-wire configuration: max. 20 Ω per conductor. |
▪ |
Open and short-circuited input permitted. |
▪ |
Open-circuit monitoring: Θ > +215°C and Θ < -40°C (Θ > +419°F and Θ < -40°F). |