MiCOM P632
Resistance Thermometer

Only PT 100 permitted for analog (I/O) module, mapping curve per IEC 75.1.

PT 100, Ni 100 or Ni 120 permitted for temperature p/c board (the RTD module).

Value range: ‑40.0°C to +215.0°C (‑40°F to +419°F).

3-wire configuration: max. 20 Ω per conductor.

Open and short-circuited input permitted.