MiCOM P632
Rapid (high-set) Differential Protection

Above the adjustable threshold DIFF: Idiff>> PSx of the differential current, the P632 will trip without taking into account either the harmonic restraint or the overfluxing stabilization. If the differential current exceeds the adjustable threshold DIFF: Idiff>>> PSx, the restraining current and the saturation discriminator are no longer taken into account either, that is the P632 will trip regardless of the restraining value and the saturation discriminator.

graphics/xhelptemp/svg2png/svg_0328_90_resolved.png

Fig. 3-98: Forming the differential and restraining currents for the three measuring systems

graphics/xhelptemp/svg2png/svg_0329_91_resolved.png

Fig. 3-99: Measuring system of the P632