MiCOM P632
Hold Time
|
The setting of the hold time defines the time period during which the IDMT protection starting time is stored after the starting has dropped out. Should starting recur during the hold time period then the time of the renewed starting will be added to the time period stored. When the starting times sum reach the tripping time value determined by the P632 then the corresponding signal will be issued. Should starting not recur during the hold time period then, depending on the setting, the memory storing the accumulated starting times value will either be cleared without delay or according to the characteristic set. In Fig. 3-127, the effect of the hold time is shown by the example of a phase current stage.
Case A: The determined tripping time is not reached.
Case B: The determined tripping time is reached.