MiCOM P632
General Starting

A general starting is triggered if the current in one phase exceeds the 1.05-fold of the set reference current value. It can be selected whether the starting of the negativesequence and residual current stages should be taken into account in the general starting decision. The general starting triggers a timer stage. A signal is issued when the time period of this stage has elapsed.

graphics/xhelptemp/svg2png/svg_0350_115_resolved.png

Fig. 3-128: General starting