Frequency Monitoring Combined with Differential Frequency Gradient Monitoring (df/dt)
|
In this operating mode of the over-/ underfrequency protection function, the frequency is also checked to determine whether the set frequency gradient is reached (in addition to being monitored for exceeding or falling below the set threshold). Monitoring for overfrequency is combined with monitoring for a frequency increase; monitoring for underfrequency is combined with monitoring for a frequency decrease. If both operate conditions are satisfied, a set timer stage is started. The timer stage can be blocked by way of an appropriately configured binary signal input.