MiCOM P632
Frequency Monitoring Combined with Mean Frequency Gradient Monitoring (Δf/Δt)

The frequency gradient can differ for system disturbances in individual substations and may vary over time due to power swings. Therefore it makes sense to take the mean value of the frequency gradient into account for load-shedding systems.

In this operating mode of over-/underfrequency protection, frequency monitoring must be set for “underfrequency monitoring”.

Monitoring the mean value of the frequency gradient is started with the starting of frequency monitoring. If the frequency decreases by the set value Δf within the set time Δt, then the Δt/Δf monitoring function operates instantaneously and generates a trip signal. If a frequency change does not lead to an operate decision of the monitoring function, then the Δt/Δf monitoring function will be blocked until the underfrequency monitoring function drops out. The trip signal can be blocked by way of an appropriately configured binary signal input.

graphics/xhelptemp/svg2png/svg_0010_128_resolved.png

Fig. 3-142: Operation of frequency monitoring combined with Δf/Δt monitoring.

graphics/xhelptemp/svg2png/svg_0401_129_resolved.png

Fig. 3-143: First stage of the over-/ underfrequency protection function