MiCOM P632
Blocking CTS

Current transformer supervision is blocked if one of the following conditions applies:

Protection is disabled (off).

The CTS function is not enabled.

An external blocking signal is present.

The general trip signal is present.

Inrush stabilization or overfluxing restraint have operated.

graphics/xhelptemp/svg2png/svg_0368_138_resolved.png

Fig. 3-153: Blocking of current transformer supervision