MiCOM P632
Monitoring Condition

If CTS is ready, it will monitor the positive- and negative-sequence currents from both transformer ends (a, b).

A CT fault is detected when the following conditions are simultaneously present:

The positive-sequence current exceeds the set threshold Ipos> in both winding ends. This means that CTS can operate only if a minimum load current is present in the protected object.

The negative- to positive-sequence current ratio exceeds a high set threshold value Ineg/Ipos>> in a single winding end.

In the other end, the negative- to positive-sequence current ratio is smaller than the low set threshold value Ineg/Ipos>, or no significant current is present (i.e. the positive-sequence current is lower than the Ipos> threshold).

In such a case, there is a fault in the secondary circuit of the CT at the transformer end where a high negative-sequence current is present.

Because this function uses negative-sequence currents, it can only detect unbalanced CT faults. In practice, this does not present a problem as the occurrence of a three-pole CT fault is very unlikely.

graphics/xhelptemp/svg2png/svg_0370_139_resolved.png

Fig. 3-154: Current evaluation referring to the respective end

graphics/xhelptemp/svg2png/svg_0369_140_resolved.png

Fig. 3-155: CTS triggering condition

N represents the number of transformer ends, that is N = 2 (a, b).